home | contact

 

Current Markets

data centers
disaster recovery
utility substation
telecom sites

DISASTER RECOVERY

Extended back up power is often required when power outage is caused by a natural disaster such as a hurricane or a major snow or ice storm. On the average, the recovery plans may take from a few days to a few weeks before the power is restored to the general public and commercial businesses. The southeast corridor of the United States is particularly prone to seasonal hurricanes but a natural gas supply typically does not exist in this geographic region. As a result, heat and hot water which also depend on electricity are also lost during a major power outage. Microcell’s MGN series, while operating on commercial hydrogen cylinders, delivers clean and quiet back up power and is also capable of providing the hot water needs of the facility. The combined heat and power feature of the MGN series increase the efficiency of the power system typically from about 30-40% (electrical) to as high as 70% (net electrical and heat).

Operation of a CHP fuel cell system in a back up mode reduces the green house gas and other harmful emissions as compared to diesel or gasoline fired generators and is significantly quieter.

Please see product specifications below:

 

PRODUCT CHARACTERISTICS
MGEN1000
MGEN3000
MGEN5000
CHP POWER PLANTS
Fuel Cell Module        
Type
PEM
PEM
PEM
PEM
Power Output (Nominal)
1000 W
3000 W
5000 W
100kW+
Output Voltage
48 Vdc
48 Vdc
48 Vdc
110-240 Vac, 48 Vdc
Output Voltage Regulation
+/- 5%
+/- 5%
+/- 5%
+/- 5%
Start Up Time
<1 min to 50% load
<1 min to 50% load
<1 min to 50% load
<1 min to 50% load
Optional Hot Water Heater        
Size
30/40 gallon
40/50 gallon
40/50 gallon
>1000 gallon
Temperature
Adjustable, 140° F max
Adjustable, 140° F max
Adjustable, 140° F max
Adjustable, 140° F max
Time to Temperature
1-2 hours
1-2 hours
1-2 hours
Varies with tank size
Combined Heat and Power Efficiency
 
85% HHV, Net >60%
85% HHV, Net >60%
85% HHV, Net >60%
85% HHV, Net >60%
Dimensions
Standard
27x25x17 inches
36x24x36 inches
36x24x36 inches
Custom (Not including fuel storage)
per customer specification
per customer specification
per customer specification
per customer specification
Fuel Supply        
Hydrogen
Industrial Grade
Industrial Grade
Industrial Grade
Ind Grade or On-Site Reformed NG
Fuel Pressure
>40 psi (supply)
5-10 psi (on board)
>40 psi (supply)
5-10 psi (on board)
>40 psi (supply)
5-10 psi (on board)
>40 psi (supply)
5-10 psi (on board)
Operation        
Warranty
1 yr
1 yr
1 yr
1 yr
Extended-Warranty (optional)
5 yr
5 yr
5 yr
5 yr
Emissions        
Water
<1 liters/hour
<2.6 liters/hour
<2.6 liters/hour
per customer specification
Noise
<65 dBA at 1 meter
<65 dBA at 1 meter
<65 dBA at 1 meter
per customer specification
Heat (if not recovered)
< 7000 BTU/hr at peak
< 19000 BTU/hr at peak
< 19000 BTU/hr at peak
N/A
Control
Microprocessor with LED
panel and alarms
Microprocessor with LED
panel and alarms
Microprocessor with LED
panel and alarms
Microprocessor with LED
panel and alarms
Monitoring
Local/Remote
Local/Remote
Local/Remote
Local/Remote

 

Microcell Corporation Logo